10 FAULT-FINDING
10.1 General (all installations)
Check the following, in sequence (by service engineer):
Step Signs Check points Actions
1 Boiler display is blank. The mains voltage 230 V Replace fuse if
necessary, but check
what circuit it was
protecting and rectify if
faulty.
The fuse in the euro-
connector
The control box fuses
2 Boiler display shows a
fault code
For flashing digits If yes, follow instructions
in the table, ref. Par. 10.2.
3 Boiler display shows
operating code
(see Par. 6.3)
0 (no heat demand)
Go to point 4.
1 to 9, h, l, b
try to find the cause of
the fault, using operating
mode shown.
4 Use boiler manual
override.
(see Par. 6.1.3)
Does the boiler start up? Yes, check external
control and wiring, or go
to point 6.
No, go to point 5.
5 Override external
controls by fitting a
link across terminals
3 and 4 of the boiler
terminal strip
Does the boiler start up? Yes, check boiler
parameters. If all OK,
then replace control box.
No, repeat point 3,or go
to point 6.