REMEHA Quinta 85 Technical Information Page 43

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 42
43
8.2.4 Boiler temperature control
The Remeha Quinta 85 has electronic temperature control with flow and return
temperature sensors. The flow temperature can be adjusted between 20 and 90°C.
8.2.5 High limit temperature protection
The high limit temperature protection device switches off and locks out the boiler when
the flow temperature exceeds the high limit set point (adjustable). When the fault is
corrected, the boiler can be restarted by using the ‘reset’-key on the control panel.
8.2.6 Low-water protection (flow and content)
The Remeha Quinta 85 is supplied with a low-water protection on the basis of
temperature measurement, see Fig. 22, Boiler sensor resistance/temp graph. By
modulating back at the moment that the water flow threatens to fall too low, the boiler
is kept operating for as long as possible. In the event of low flow (F/R dt = 45°C), the
boiler will shut off and not lockout (ref. Par. 6.4).
If the boiler is fired dry, it will go to high temperature lock out, failure code 1*
8.3 External connections
All external connections (except rematic
®
2945 C3K) are made on the 24 way terminal
strip, located in the instrument box at the bottom of the boiler, accessed by loosening
the two screws, see Fig. 13 and Fig. 14.
Fig. 13 Terminal strip Remeha Quinta 85
04.W4H.79.00009
*) remove link to use, see Par. 8.8
24
BUS
(Tmax)
+
GND
T
T
T
L
L1
N
~
230V
14
10
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
24V
~
PWM
N
L1
L
230V
~
External interlock - volt free
Tmax
14
12
1
7
4
2
3
6
5
10
9
8
10
11
PWM
230V signal to BMS power supply live
Boiler pump or system pump (max. 1Amp)
DHW diverting valve or primary pump
Boiler run volt free (closes on run)
Common alarm volt free (opens on failure)
Not UK boiler
19
16
13
15
17
18
22
20
21
24
23
T
T
T
BUS
DHW sensor or volt free thermostat
0-10V or modulating controller
High / low ( 2nd stage) or
outdoor sensor
ON / OFF (1st stage)
Not UK boiler
*
Page view 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 67 68