REMEHA Quinta 85 Technical Information Page 29

  • Download
  • Add to my manuals
  • Print
  • Page
    / 68
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 28
29
Code Description Example 5250 r/m
,
Fan speed
52 hundreds
>
Fan speed
50 units
Table 11 Fan speed mode service level
6.9 Failure mode (x00)
To check the latest failure with the accompanying operating codes and relevant
temperatures.
Using the ‘m -key, press repeatedly until 1 (flashing digit) appears in the ‘code’-
display.
Then select the required code 2, 3 or 4 etc. using the ‘s’-key and read off the
relevant value.
Code
t
Description
137
Display of failure code (see Par. 10.2)
203
Operating mode during failure
353
Flow temperature during failure
440
Return temperature during failure
560
DHW temperature during failure
63&
n/a
Table 12 Failure mode on service level
Example as above:
Failure code 37 indicates the return temperature sensor failed during HTG operation
(03), at a flow temperature of 53°C, a return temperature of 40°C and DHW
temperature of 60°C.