7 INSTALLATION INSTRUCTIONS
7.1 General
The complete installation must comply with the current editions of relevant British
Standards and codes of practice, including the latest local and national regulations for
this type of equipment.
All gas appliances must, by law, be installed by a competent qualified engineer
registered with CORGI and holding the relevant qualifications and certificates (for
example ACOPS and IEE regs.)
Important:
The Remeha Quinta 85 is a CE certified appliance and must not therefore be modified
or installed in any way contrary to these “Installation and Maintenance Instructions”.
These manufacturer’s Instructions must NOT be taken as overriding statutory
obligations. Failure to install this appliance correctly could result in an unsafe condition
which can lead to prosecution. It is your own interest and that of safety to ensure that
the law is complied with.
7.2 Location
The remeha Quinta 85 is primarily
designed for wall mounting (on the
bracket supplied). The wall should be
flat, vertically plumb and capable of
supporting the full weight of the boiler full
of water. An optional floor frame can be
used for a free standing installation or
where the wall cannot carry the weight.
The following minimum clearances are
required:
- Front: 600 mm
- Sides: 25 mm
- Bottom: 250 mm
- Top: 400 mm.
Fig. 05 Minimum clearances around
the boiler