21
6.5.1 Flow temperature set point (!)
The required flow temperature is adjustable from 20 to 90°C (factory default 80°C).
Fig. 04 Typical setting change procedure
pdf
6.5.2 Pump run on time HTG (@)
Pump run on time can be adjusted (Please refer to installation contractor)
- Press the ‘m’ -key until the digit ! (with dot) appears in the ‘code’-display.
- Press the ‘s’-key until the digit @ (with dot) appears in the ‘code’-display.
- Set the required value, using the [+] and [-]-keys.
- Press the ‘e’-key to store the new value (value will flash twice).
- Press the ‘reset’-key to return to operating mode.
NOTE: For continuous pump operation use manual override, see Par. 6.1.3.
Code
t
Description
@00
Pump runs on for 10 seconds
@Xx Pump runs on for 1 to 15 minutes (xx = 01 to 15)
Table 07 Pump run on time HTG