3.4 Options
- Floor frame.
- Two pipe flue/air inlet adapter plate (excentric room sealed).
- DHW-sensor.
- Weather compensating controllers.
- Heat exchanger cleaning tool.
- EMC filter for boiler sensor or boiler thermostat cables
(when sensor wires exceed 3 m. length).
4 EFFICIENCY INFORMATION
4.1 Annual efficiency
108% at H
i
at an input of 30% and a return temperature of 30°C.
4.2 Heat to water efficiency
a. Up to 98% at Hi at an average water temperature of 70°C (80/60°C).
b. Up to 108% at Hi at an average water temperature of 40°C (50/30°C).
NOTE: NCV = H
i
, GCV = H
s
5 APPLICATION INFORMATION
The Quinta 85 can be used on all new and re-furbishment projects in both single and
multiple configurations. Conventional and room sealed flue system capability means
that the boiler can be sited almost anywhere within a building.
The Remeha range of weather compensators (options) are able to communicate
directly with the boiler controls (two wire) to make full use of it’s fully modulating
feature, ensuring that the boiler closely matches the system demand at all times.
External control systems (BMS) can be interfaced with the boiler to provide on/off -
high/low or modulating (0 -10 V) control options.