3.2 Technical data
Boiler type Quinta 85
General
Colour side and front casing
Colour instrument panel flap
BS RAL
9016
7036
Boiler control options (External input)
(Two wire control)
On/off, High/low, Analog 0 -10V
Communicating Modulation
Nominal output (80/60ºC) kW 14.1 - 84.2
Nominal output (50/30ºC) kW 15.8 - 89.5
Nominal input (GCV / H
s
) kW 16.2 - 95.3
Nominal input (NCV / H
i
) kW 14.6 - 86.0
Weight dry kg 72
Noise level at 1 m from boiler dB(A) < 52
Gas- and flue details
Category II
2H3P
Min/Max Inlet pressure natural gas mbar 17 - 30
Min/Max Inlet pressure propane mbar 37 - 50
Gas consumption (natural gas) m
3
/h 1.5 - 9.1
Gas consumption (propane) m
3
/h 0.6 - 3.5
NO
x
-emission *) mg/kWh < 47
NO
x
-emission (O
2
= 0%, dry) *) ppm < 27
Residual fan duty Pa 160
Mass flue rate kg/h 23 - 138
Classification due to discharging flue
gases
B23, C13, C33, C43, C53,
C63, C83
Water side
Maximum flow temperature
ºC 100 (110)
Operating flow temperature ºC 20 - 90
Operating pressure min. (open vented) bar 0.3
Operating pressure min. (pressurised) bar 0.8
Operating pressure max. bar 4.0