Remeha Gas 360 S 20/07/05 - 300005180-001-A
4 Setting the start up pressure
If necessary, the start-up pressure can be set on the right valve (1st
stage) using a flat screwdriver.
In the factory, it is set to maximum..
To modify this setting, it necessary first to remove the protection
using a screwdriver (1/4 turn).
The progressivity of the left valve (2nd stage) is always set to
"Minimum".
No setting is needed on the left valve on a 14-element boiler.
1/4 turn
Natural gas
or
Propane
Natural gas H Propane
Start-up pressure 11 mbar 10 mbar
Recommended position "Maxi"
between "Mini" and "Maxi" (1/4
turn)