Gas 110 Eco 115 / 65Gas fired condensing boilerRemeha Gas 110 EcoInstallation, User and Service ManualRemeha300014883-001-KEN
10Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K3.5 Technical dataGas 110 Eco 65 115CE identification no **** CE-0063BS3826Boiler specificationsPow
1125/01/2011 - 300014883-001-K Gas 110 Eco 115 / 653.6 Main dimensions3.6.1 Boiler self-standing• Gas 110 Eco 115 / 65R = ThreadG = Exterior cylindric
12Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K3.6.2 Boiler installedClear space should be left around the boiler:- 70 cm in front of the boiler-
1325/01/2011 - 300014883-001-K Gas 110 Eco 115 / 653.7 Hydraulic specificationsDepending on the flow, the following diagrams represent:- the manometri
14Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K4 Control and safety equipment4.1 Control panel4.1.1 GeneralThe boiler is supplied with a standard
1525/01/2011 - 300014883-001-K Gas 110 Eco 115 / 654.1.3 Combined key functions (in operating mode only)When the boiler is in the operating mode, keys
16Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K4.2 Flow diagram control systemPress the "r"-key for the menu Press the "w"-key
1725/01/2011 - 300014883-001-K Gas 110 Eco 115 / 654.3 Operating mode (N>>)During operation the "code"-display shows the status (posit
18Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K4.4 Shut-off mode (B<<)During shut-off mode condition the "code"-display will show
1925/01/2011 - 300014883-001-K Gas 110 Eco 115 / 654.5.1 Flow temperature set point ()The required flow temperature is adjustable from 20 to 90 °C.4.
2Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-KDeclaration of conformity 1The appliance complies with the standard model described indeclaration of
20Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K4.5.3 DHW temperature set-point ( )The DHW temperature is adjustable from 20 to 75 °C (factorydefau
2125/01/2011 - 300014883-001-K Gas 110 Eco 115 / 654.6 Setting mode service level (<)(only for the qualified service engineer with product knowle
22Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K4.6.1 Flow temperature set point during forced part load ()Adjustable from 20 °C to 90 °C. This v
2325/01/2011 - 300014883-001-K Gas 110 Eco 115 / 654.6.7 DHW cut-in temperature (+)Adjustable from °C to °C (8 steps).ZSee chapter 4.6. TableDHW
24Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K4.6.14 Maximum delay time (;)Adjustable from to && minutes.This value sets the maximum o
2525/01/2011 - 300014883-001-K Gas 110 Eco 115 / 654.7 Read-out mode (<)To check boiler set points and values.Using the "r" - key, pres
26Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K5 Installation5.1 Statutory terms and conditions of installation and maintenanceThe complete instal
2725/01/2011 - 300014883-001-K Gas 110 Eco 115 / 655.2 Important comments on the treatment of the heating circuit Water treatment- Use untreated tap
28Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K Minimum water flowThe maximum temperature difference between flow and return, andthe maximum rate
2925/01/2011 - 300014883-001-K Gas 110 Eco 115 / 655.3 Water discharge connectionDischarge condensation water directly into the main drain. Given thed
325/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65Contents1 Used symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
30Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K5.6 Reversal of the direction the control panel access door opensAs standard, the control panel acc
3125/01/2011 - 300014883-001-K Gas 110 Eco 115 / 651 23C001495C001496
32Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K5.7 LevellingLevel the boiler by turning the adjustable feet. To adjust, take the loadoff the foot
3325/01/2011 - 300014883-001-K Gas 110 Eco 115 / 656 Connecting the flue6.1 Flue pipe connections- The horizontal sections on the flue gas side will b
34Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K6.1.1 Classification6C0012461227 333 4 251 Flue type C13: Air/flue gas connection by means of conce
3525/01/2011 - 300014883-001-K Gas 110 Eco 115 / 656.1.2 Lengths of the air/flue gas pipesLmax is measured by adding the lengths of the air/flue gasp
36Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K6.2 Electrical connectionThe Gas 110 Eco 115 / 65 must have a fixed 230V - 50Hz singlephase mains
3725/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65 Access to the electrical connections` Open the panel flap.`Unscrew the 2 mounting screws at the
38Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K7 Start-upInitial commissioning must be done by a qualifiedprofessional.7.1 Filling the system` Fi
3925/01/2011 - 300014883-001-K Gas 110 Eco 115 / 657.3 Putting the appliance into operationC001490-B31244C001491-B5C001492-B6C001493-B7
4Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K5.2 Important comments on the treatment of the heating circuit. . . . . . . . . . . . . . . . . . .
40Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K7.3.1 Gas 110 Eco 65 The boiler is preset in the factory to operate on natural gas G20.Connection p
4125/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65` Set the burner output to minimum using the "r" and [-]-keyssimultaneously.H : Minimum o
42Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-KWhen the setting is correct:` Press the [+] and [-]-keys simultaneously to return in operatingmode.
4325/01/2011 - 300014883-001-K Gas 110 Eco 115 / 658 Fault finding8.1 General (all installations)Check the following, in sequence (by service engineer
44Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K8.2 Fault codesIn the event of an error message, both the "code"-display and the x-displa
4525/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65 Return temp > flow temp - Flow sensor badly installed- Pump operating in wrong direction or f
46Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K9 Adapting to another gas typeThese actions must be carried out by a qualified engineerholding the
4725/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65 Gas 110 Eco 115Changing from Natural Gas to Propane requires:- Installing the conversion kit (fit
48Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K10 Maintenance10.1 GeneralThe boiler requires little maintenance if it is correctly set. The boiler
4925/01/2011 - 300014883-001-K Gas 110 Eco 115 / 6510.2.2 Setting the ignition electrode- Check the setting of the ignition electrode. Set the gap bet
525/01/2011 - 300014883-001-K Gas 110 Eco 115 / 651 Used symbolsCaution dangerRisk of injury and damage to equipment. Attention must bepaid to the wa
50Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K10.3 Cleaning and maintenanceBefore any operation, ensure that:- The mains supply is disconnected,
5125/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65 Operational modeIf the boiler requires cleaning, carry out the following maintenanceoperations:-
52Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K Cleaning the heat exchangerSpecific tools: Cleaning toolZSee chapter Spare parts Gas 110 Eco 65:
5325/01/2011 - 300014883-001-K Gas 110 Eco 115 / 6510.4 Maintenance of the air/flue gas drain connection fluesThe connection pipes must be checked at
54Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K11 Schematic diagrams Safety box Operation Display (Not used) Ignitor + Ionization probe Trans
5525/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65 Skeleton Diagrams PRINCIPLE DIAGRAM GAS 110 ECOMCBAVN12X24D I S P L A YPC SERVICE1 / 14X71 / 14
56Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K12 Spare parts - Gas 110 Eco 115 / 6526/10/2010 - 300014883-002-ETo order a spare part, give the r
5725/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65Casing - Gas 110 Eco 65C 15100 1103107106104108108109105101102110100105
58Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-KBoiler body - Gas 110 Eco 115492C001513-C
5925/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65Casing - Gas 110 Eco 115503507506504508508508509505501502500505C001514
6Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K3 Description3.1 GeneralGas 100 Eco 115 / 65 boilers are floor standing gas-fired condensingboilers
60Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-KMark. Reference DescriptionBoiler body - Gas 110 Eco 65 1 200010067 Complete sealed air box2 S46850
6125/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65410 97860646 Adjustable foot M10x35411 200009369 Complete box door413 S44698 Temperature sensor ELM
62Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K
6325/01/2011 - 300014883-001-K Gas 110 Eco 115 / 65
© CopyrightAll technical and technological information contained in these technical instructions, as well as anydrawings and technical descriptions su
725/01/2011 - 300014883-001-K Gas 110 Eco 115 / 653.3 Main parts• Gas 110 Eco 65C001484125436121310119871 Fan air inlet2 Return sensor3 Heating body4
8Gas 110 Eco 115 / 65 25/01/2011 - 300014883-001-K• Gas 110 Eco 11512131011987125436C0014851 Fan air inlet2 Return sensor3 Heating body4 Heat exchange
925/01/2011 - 300014883-001-K Gas 110 Eco 115 / 653.4 Technical characteristics3.4.1 Boiler- For operation on Natural Gas or Propane (See "Switch